- Rated Operational Voltage:208 ... 600 V AC
- Rated Control Supply Voltage (Us):24 V AC/DC
- Rated Control Circuit Voltage (Uc):DC Operation 24 V
- Rated Frequency (f):50/60 Hz
- Main Circuit 50 / 60 Hz
- Rated Operational Power - In-Line Connection (Pe):
- (230 V) 22 kW
- (400 V) 37 kW
- (500 V) 45 kW
- Rated Operational Current - In-Line Connection (Ie):72 A
- Service Factor Percentage:100 %
- Overload Protection:Recommended MS495 57 ... 75
- Integrated Electronic Overload:No
- Adjustable Rated Motor Current Ie:No
- Starting Capacity at Maximum Rated Current Ie:4xIe for 6s
- Ramp Time:
- 0 ... 20 second [unit of time]
- 1 ... 10 second [unit of time]
- Initial Voltage During Start:40 ... 70 %
- Step Down Voltage Special Ramp:100 ... 60 %
- Current Limit Function:No
- Switch for Inside Delta Connection:No
- Run Signal Relay:Yes
- By-pass Signal Relay:Yes
- Fault Signal Relay:No
- Overload Signal Relay:No
- Signal indication completed start ramp (LED):Green
- Signal indication ready to start/standby ON (LED):Green
- Signal indication running R (LED):Green
- Signal indication ramping up/down (LED):Green
- Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time:10
- Communication:FiledBusPlug(Optional)
- Degree of Protection:IP10
- Terminal Type:Main Circuit: Bars
- Connecting Capacity Main Circuit:
- Rigid 1x 6 ... 95 mm²
- Rigid 2 x 6 ... 35 mm²
- Connecting Capacity Control Circuit:
- 1 x 0.75 ... 2.5
- 2 x 0.75 ... 2.5 mm²
- Rigid 1/2 x 0.75 ... 2.5 mm²
- Connecting Capacity Supply Circuit:Rigid 1 x 0.75 ... 2.5 mm²
- Tightening Torque:
- Control Circuit 0.6 N·m
- Main Circuit 8 N·m
- Supply Circuit 0.6 N·m
Bình luận