- Current Type: AC
- Electrical Durability:
- Ue =< 440 V 5000 cycle
- Ue = 500 ... 690 V 4000 cycle
- 20 cycles per hour
- Mechanical Durability:
- 15000 cycle
- 60 cycles per hour
- Neutral Pole Current ([%Iu]): 100 %
- Number of Poles: 4
- Power Loss: 900 W
- Product Main Type: SACE Emax 2
- Product Name: Air Circuit Breaker
- Product Type: Air Circuit Breaker
- Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
- Rated Current (In): 4000 A
- Rated Voltage (Ur): 690 V
- Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
- Rated Insulation Voltage (Ui): AC 1000 V
- Rated Operational Voltage: 690 V AC
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (220 V AC) 85 kA
- (230 V AC) 85 kA
- (380 V AC) 85 kA
- (400 V AC) 85 kA
- (415 V AC) 85 kA
- (440 V AC) 85 kA
- (500 V AC) 66 kA
- (660 V AC) 66 kA
- (690 V AC) 66 kA
- Rated Short-time Withstand Current Low Voltage (Icw):
- for 1 s 66 kA
- for 3 s 66 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (400 V AC) 85 kA
- (415 V AC) 85 kA
- (440 V AC) 85 kA
- (500 V AC) 66 kA
- (525 V AC) 66 kA
- (690 V AC) 66 kA
- Rated Uninterrupted Current (Iu): 4000 A
- Release: Ekip Dip LSIG
- Release Type: EL
- Short-Circuit Performance Level: S
- Standards: IEC
- Sub-type: E4.2
- Version: W
Bình luận